AUTHORIZED DISTRIBUTOR
PACK OF 2
Product Features
- Tuning of residential and furnaces and domestic boilers
- Ambient and stack testing for CO
- CO safety measurements in and around combustion sources
- Temperature checking, including superheat and hydronic differential temperatures
- Dual input differential manometer
Combustion Analyzer. Measure CO, O2 and differential temp. and pressure, calculate CO2
Features
- Fast and easy set-up
- Built in high-resolution (0.001 inH2O) differential manometer
- Measures CO, O2, pressure, and temperature
- Calculates CO2, efficiency, excess air, and CO air free
- IR printer port ? use optional A740 infrared printer
- Selectable fuels: natural gas, light oil, heavy oil, LPG, bituminous coal, anthracite coal, coke, butane, wood, bagasse
- Pump driven for fast response
- Flue probe with built in thermocouple
- Soft carrying case
- Protective rubber boot
- Available with rechargeable battery
WHAT'S IN THE BOX
- 709 Combustion Analyzer
- Flue Probe with K-Type A770
- K-Type Temperature Probe GK11M
- In-Line Filter Complete A762
- Mini Pump Protection Filter Assembly A763
- Carrying Case A768
- Protective Rubber Boot A765
Applications:
- Tuning of residential and furnaces and domestic boilers
- Ambient and stack testing for CO
- CO safety measurements in and around combustion sources
- Temperature checking, including superheat and hydronic differential temperatures
- Dual input differential manometer
Specifications:
- Carbon Monoxide (CO) Measurement Range 0 to 10,000 ppm, Resolution 1 ppm, Accuracy +/-5ppm or 5% of reading whichever is greater
- Oxygen (02) Measurement Range 0 to 25%, Resolution 0.1%, Accuracy ±0.3%
- Carbon Dioxide (CO2) Range 0 to 25%, Resolution 0.1%, Accuracy Calculated
- Nitric Oxide Measurement N/A
- NOX Measurement N/A
- Temperature Measurement Range -40 to 1472°F, or -40 to 800°C, Resolution 1°F or °C, Accuracy (K-type) ±0.3%, ±2°F or ±1°C
- Draft/Pressure Measurement Selectable Ranges mBar,kPa, and inH2O, Ranges -150 mBar to +150 mBar -15 kPa to +15 kPa -60 inH2O to +60 in H20, Resolution 0.001 inH2O, Accuracy ±0/5% fsd
- Gross/Net Efficiency Range 0 to 100%, Resolution 0.1%, Accuracy Calculated
- CO/CO2 Ratio Range 0 to 0.999, Resolution 0.001, Accuracy Calculated
- Operating Temperature 14°F to 122°F (-10°C to 50°C)
- Battery Type 1.5V AA (3)
- Selectable Fuels Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane, Wood, Bagasse
- Display Type Backlit 3 line LCD
- Data Storage 50 Locations
- Data Logging N/A
- Print Capability Yes, via optional IR printer (A740)
- PC Communication N/A
- Date & Time Function 24 Hour Real Time Clock
- Dimensions 200mm x 90mm x 60mm
- Weight 500g
- Conformity BS7927 (and the draft BS7967)